HRV / ERV INSTALLATION AND OPERATING INSTRUCTIONSToll Free: 1.800.810.3473 (Canada) 1.866.890.6457 (U.S.A.) 790 Rowntree Dairy Roa
HRV and ERV Typical Installations (cont’d)8HORIZONTAL • 30” clearance is recommended for cleaning of the core/servicing the unit.• Dampers are install
Drain Connection During defrost cycle the HRV unit may produce some condensation and the water should flow into a nearby drain.The HRV cabinet has pre
Air Flow Balancing 10Pitot Tube Airflow Balancing The following is a method of field balancing an HRV/ERV using a Pitot tube advantageous in situation
Air Flow Balancing (cont’d)DUCT DIAM.5"6"7"CROSS SECTION AREA0.136 sq. ft.0.196 0.267 sq. ft.sq. ft.The accuracy of the flow reading wi
12PROBLEMS SOLUTIONSPOSSIBLE CAUSES1. Air flow is low- HRV/ERV airflow improperly balanced- filter clogged- core obstructed- exterior fresh air supp
Troubleshooting (cont’d)13- temperature sensor failure - replace temperature sensorLED’s on the Main Control board and the remote wall mount Timer Swi
Climate Zone14Select HRV/ERV for your Climate ZoneHRVs are recommended for colder climates.ERVs are designed for warm-humid climates with long cooling
IMPORTANT READ AND SAVE THESE INSTRUCTIONS SAFETY INSTRUCTIONSwww.reversomatic.com • [email protected] WARNING! !TO REDUCE THE RISK OF FIRE, E
Parts List1ReferenceDescriptionPart no.RHRV-S100ARHRV-S100PRERV-S100QTY.QTY.QTY.1HRV / ERV - Lid, Pan Assembly93151112Polypropylene Collar 5” Dia. 014
18*16*14*Optional Parts:15*17*41255289133101112a76126RHRV-C100A RHRV-C100P RERV-C100Parts List2 Project Condo Unitmodel:RHRV-C100AAluminum CoreRHRV-C1
Parts List3ReferenceDescriptionPart no.RHRV-P100ARHRV-P100PRERV-P100QTY.QTY.QTY.1HRV / ERV - Lid, Pan Assembly93151112Polypropylene Collar 5” Dia. 014
Parts List4ReferenceDescriptionPart no.RHRV-E100ARHRV-E100PRERV-E100QTY.QTY.QTY.1HRV / ERV - Lid, Pan Assembly93151112Polypropylene Collar 5” Dia. 014
Wiring Diagram (Superior, Project Series and Project Condo Unit) 5CONTROL BOARD:a) Timer Switch (TC100)b) Wall Switchc) Dehumidistat d) Time Delay Swi
Low Voltage+5DAT CSpeedContactL0/HISpeed HV InputRemote0n/0ff HVNCCN0Ext. InterlockHIGH VOLTAGELow Voltage+5DATCSpeedContactL0/HISpeed HV InputRemote0
HRV and ERV Typical Installations72 Single VentsSVE-50 and SVI-50 Shown, 5 ft. minimum gap between vents“Fresh Air/ Exhaust Air Vents Installation”HRV